How much voltage drop occurs in a 100 ft extension cord?
Updated · 3 min read
A long extension cord can deliver noticeably less voltage than the outlet supplies under load. The voltage drop calculator estimates the loss from current, one-way length, conductor material, and size. Lower AWG numbers identify larger conductors, which generally reduce resistance and drop.
Use the cord voltage drop calculator for comparisons, not as permission to exceed a cord label. The model uses a copper resistance constant referenced to 75 degrees Celsius. Actual flexible cords, conductor temperatures, connectors, and supply wiring can produce different results.
Try the Voltage Drop Calculator
Enter your own numbers. Nothing you type leaves your device.
Use one-way length and the actual operating current
Enter 100 feet for a 100-foot cord. For a single-phase circuit, the formula already includes the outgoing and returning conductors through a factor of two. Entering 200 feet would double-count the circuit length and exaggerate the predicted drop. Select copper for the examples in this article.
Use operating current from the equipment information rather than guessing from plug shape. Starting current for motors can be higher than steady operation, and the simple calculation does not simulate that transient. If multiple devices share the cord, the relevant steady current is their simultaneous total, subject to the cord and circuit ratings.
Work through the 12 AWG example
The imperial formula is two times K times current times one-way feet divided by conductor area in circular mils. Using K equal to 12.9 and 6,530 circular mils for 12 AWG, the calculation is 2 times 12.9 times 10 times 100 divided by 6,530.
The result is 3.951 volts. Divide by a 120-volt source and multiply by 100 to get 3.292%. Subtract the loss from 120 to estimate 116.05 volts at the load. That assumes the source remains at 120 volts under load; upstream wiring losses can lower the actual starting voltage.
Compare gauges at several loads
The table shows voltage loss, not approved load capacity. The 16 AWG row is an extension of the same formula using an assumed nominal 2,580 circular mil area; the site selector itself begins at 14 AWG. Verify the exact cord construction and rating before relying on a gauge comparison.
Some cells describe conditions that may exceed a particular cord label or equipment instruction. They are mathematical comparisons only, especially for the smaller gauge at higher current. A larger conductor can reduce voltage drop without making damaged insulation, unsuitable plugs, or an overloaded supply circuit acceptable.
| AWG | 5 amps | 10 amps | 15 amps |
|---|---|---|---|
| 16, supplemental model | 5.00 | 10.00 | 15.00 |
| 14 | 3.14 | 6.28 | 9.42 |
| 12 | 1.98 | 3.95 | 5.93 |
| 10 | 1.24 | 2.49 | 3.73 |
Interpret the three and five percent guidelines
Common NEC informational guidance recommends about 3% maximum branch-circuit drop and 5% combined feeder-plus-branch drop for reasonable operation. These are not a universal rule authorizing any extension-cord setup. Particular equipment and installations may have additional requirements, and local code adoption matters.
At 120 volts, 3% is 3.6 volts and 5% is 6 volts. The modeled 12 AWG cord at 15 amps loses 5.93 volts, nearly consuming the entire 5% budget before upstream losses. The calculator status colors summarize its percentage thresholds, not an inspection of the cord or a determination of legal ampacity.
Treat RV and outdoor use as equipment-specific
For an RV, use an RV-rated connection system and follow the RV and cord manufacturer instructions. Air conditioners and other motor loads can be sensitive to low supply voltage. A general household extension cord should not be treated as an equivalent replacement for a properly rated RV shore-power assembly.
Inspect plugs and insulation, follow outdoor-use and GFCI requirements, and avoid improvised adapters or daisy-chained cords. Follow instructions about fully deploying cord reels under load. Stop using equipment if connections become hot or damaged, and have a licensed electrician evaluate persistent voltage problems or any permanent wiring changes.
Frequently asked questions
Enter the one-way 100-foot length. The single-phase formula already accounts for the outgoing and return conductors.